CK5W-36/102

Specifications

Specification Conditions Value
VRMS AC 28800 VAC
IMAX For 8 x 20 μs Pulse 5000 A
VR (L-N) 36 kV
VDC REF At 1 mA 51.6 kV
VRES At Steep of 1 x 10 µs Pulse 122.4 kV
VRES For Lightning Impulse 8 x 20 µs 105.6 kV
VRES For Switching Impulse 30 x 60 µs 90 kV
ISWC For Current Impulse 4 x 10 µs 65 kA
VBIL For Lighning Impulse 138 kV
VBIL At Power Frequency, Wet 1 Minute 96 kV
Str. Tor. 50 N m
Str. Can. 147 N m
Creepage 962 mm
A 1.18 in.
B 1.18 in.
C 15.511 in.
D 17.875 in.
E 2.047 in.
F 4.331 in.

Notes

  • Meets IEC600 99-4.
Pararrayos de lineas de transmisión eléctrica