ARD32X3
Specifications
Specification | Conditions | Value |
---|---|---|
VR | 0.28 V | |
VTV | At IR | 0.48 kV (DC) |
IR | At VTV | 150 μA |
VDC MIN | At 1 mA | 0.6 kV |
VDC MAX | At 1 mA | 0.8 kV |
VRES Ratio | At 5 kA, For 8 x 20 μs Pulse | 1.88 kV |
IIMP | For 4 x 10 μs Pulse | 40 kA |
IIMP | 2 ms | 100 kA |
Dia | Plus or Minus 1 mm | 32 mm |
TMAX | Plus or Minus 1 mm | 3 mm |
Op. Temp. | 55 to 125 °C | |
Store Temp. | 55 to 125 °C |
Notes
- Device data taken at 25 °C.
- Typical response time is less than 15 nanoseconds.
- Arrester discs may be used in porcelain or silicon rubber housing, medium can be air or SF6 or equivalent.
- Meets IEC600 99-4.